A 200 bus power system has 160 PQ bus. For achieving a load flow solution by N-R in polar coordinates, the minimum number of simultaneous equation to be solved is ___________?
0
votes
asked
Nov 11, 2022
in
Power System
by
Robin
A 200 bus power system has 160 PQ bus. For achieving a load flow solution by N-R in polar coordinates, the minimum number of simultaneous equation to be solved is ___________?
a) 334
b) 359
c) 357
d) 345
power-system
Please
log in
or
register
to answer this question.
1
Answer
0
votes
answered
Nov 11, 2022
by
Robin
Total number of equation = (40-1)*1 + (160*2) = 359
...